Print Back
Applications
Medium-Voltage power cables offer an economical, rugged and reliable alternative to labor-intensive cable in conduit wiring methods.
Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced not more than six feet apart.
Installed in both exposed andmore
UL Type MV-105 AL
Items UL Type MV-105 AL
A4-03MV5UT10501
PowerGuard® 5kV 133% AL 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07
UL Type MV-105 AL
A2-03MV5UT10501
PowerGuard® 5kV 133% AL 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07
UL Type MV-105 AL
A1-03MV5UT10501
PowerGuard® 5kV 133% AL 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07
UL Type MV-105 AL
A1/0-03MV5UT10501
PowerGuard® 5kV 133% AL 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07
UL Type MV-105 AL
A2/0-03MV5UT10501
PowerGuard® 5kV 133% AL 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07
Size
AWG
or
KCMIL
N/A 4 N/A 2 N/A 1 N/A 1/0 N/A 2/0
Insulation
Thickness
(mil)
N/A 115
No. of
Ground
Wires
N/A 3
Size
AWG
of
Ground
Wires
N/A 10 N/A 10 N/A 10 N/A 10 N/A 8
Conductor
Diameter
(in)
N/A 0.226 N/A 0.284 N/A 0.324 N/A 0.364 N/A 0.408
Insulation
Diameter
(in)
N/A 0.5 N/A 0.56 N/A 0.6 N/A 0.64 N/A 0.69
Insulation
Shield
Diameter
(in)
N/A 0.56 N/A 0.62 N/A 0.66 N/A 0.7 N/A 0.74
Overall
Jacket
Diameter
(in)
N/A 1.42 N/A 1.55 N/A 1.64 N/A 1.78 N/A 1.88
Approximate
Weight (lb/MFT)
N/A 929 N/A 1095 N/A 1200 N/A 1429 N/A 1645
Minimum
Bending
Radius
(in)
N/A 10 N/A 11 N/A 12 N/A 13 N/A 14
Ampacity
90ºC
in Duct
N/A 80 N/A 105 N/A 120 N/A 140 N/A 160
Ampacity
90ºC
in Air
N/A 81 N/A 110 N/A 125 N/A 145 N/A 170