Applications
Construction
Conductor: Class A or B Compressed concentric stranded aluminum alloy 1350 per ASTM B 231. Stranded conductors are water-blocked with conductor filling compound.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire: Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core
Jacket: Black, sunlight resistant, flame retardant PVC jacket
Specifications
NOTES:
Items |
A1/0-03AIAPC35GT105 PowerGuard® Armored 35kV 100% AL 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
A2/0-03AIAPC35GT105 PowerGuard® Armored 35kV 100% AL 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
A3/0-03AIAPC35GT105 PowerGuard® Armored 35kV 100% AL 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
A4/0-03AIAPC35GT105 PowerGuard® Armored 35kV 100% AL 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
A250-03AIAPC35GT105 PowerGuard® Armored 35kV 100% AL 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
|||||
Size AWG or KCMIL |
N/A 1/0 | N/A 2/0 | N/A 3/0 | N/A 4/0 | N/A 250 | |||||
Insulation Thickness (mil) |
N/A 345 | |||||||||
No. of Ground Wires |
N/A 3 | |||||||||
Size AWG of Ground Wires |
N/A 10 | N/A 8 | N/A 8 | N/A 8 | N/A 8 | |||||
Conductor Diameter (in) |
N/A 0.336 | N/A 0.379 | N/A 0.423 | N/A 0.479 | N/A 0.522 | |||||
Insulation Diameter (in) |
N/A 1.08 | N/A 1.13 | N/A 1.17 | N/A 1.23 | N/A 1.27 | |||||
Insulation Shield Diameter (in) |
N/A 1.16 | N/A 1.2 | N/A 1.24 | N/A 1.3 | N/A 1.35 | |||||
Overall Jacket Diameter (in) |
N/A 2.95 | N/A 3.04 | N/A 3.14 | N/A 3.28 | N/A 3.38 | |||||
Approximate Weight (lb/MFT) |
N/A 3395 | N/A 3680 | N/A 3938 | N/A 4321 | N/A 4616 | |||||
Minimum Bending Radius (in) |
N/A 21 | N/A 22 | N/A 22 | N/A 23 | N/A 24 | |||||
Ampacity 105ºC in Duct |
N/A 165 | N/A 185 | N/A 210 | N/A 240 | N/A 265 | |||||
Ampacity 105ºC in Air |
N/A 185 | N/A 215 | N/A 245 | N/A 285 | N/A 315 | |||||
|