Print Back
Applications
To supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volts or lower at a conductor temperature of 75 ºC maximum.

Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand ACSR neutral messenger.

Standards
  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
  • B-231 Aluminum Conductors, Concentric-Lay-Stranded.
  • B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
  • B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
  • B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
  • Duplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
Unit of Measure

Specifications

Code Name

Bull

Phase
Conductor
Size/AWG

1/0

Phase
Conductor
Stranding

19/w

Phase
Conductor
Insulation
Thickness

60 mls

Bare
Neutral
Messenger
Size/AWG

1/0

Bare
Neutral
Strand

6/1

Bare
Neutral
Messenger
Breaking
Strength

4380 Lbs

Weight
Per
(lb/1000 ft)
XLP

288.7 Lbs

Weight
(lb/1000 ft)
Poly

280.3 Lbs

Ampacity
XLP

205 Amps

Ampacity
Poly

160 Amps