Applications
Medium-Voltage power cables offer an economical, rugged and reliable alternative to labor-intensive cable in conduit wiring methods.
Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced not more than six feet apart.
Installed in both exposed and concealed work, wet or dry locations, directly buried.

Construction
Conductor: Class B Compressed concentric strand or soft drawn annealed copper per ASTM B3.
Conductor Shield: Extruded thermosettingmore

Items
UL Type MV-105 CU

PowerGuard® 35kV CU 133% 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07

UL Type MV-105 CU

PowerGuard® 35kV CU 133% 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07

UL Type MV-105 CU

PowerGuard® 35kV CU 133% 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07

UL Type MV-105 CU

PowerGuard® 35kV CU 133% 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07

UL Type MV-105 CU

PowerGuard® 35kV CU 133% 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07
Size
AWG
or
KCMIL
N/A 1/0 N/A 2/0 N/A 3/0 N/A 4/0 N/A 250
Insulation
Thickness
(mil)
N/A 420
No. of
Ground
Wires
N/A 3
Size
of
Ground
Wires
N/A 8 N/A 8 N/A 7 N/A 7 N/A 7
Conductor
Diameter
(in)
N/A 0.364 N/A 0.408 N/A 0.458 N/A 0.515 N/A 0.561
Insulation
Diameter
(in)
N/A 1.26 N/A 1.3 N/A 1.35 N/A 1.41 N/A 1.46
Insulation
Shield
Diameter
(in)
N/A 1.33 N/A 1.38 N/A 1.43 N/A 1.48 N/A 1.54
Overall
Jacket
Diameter
(in)
N/A 3.21 N/A 3.31 N/A 3.41 N/A 3.54 N/A 3.65
Approximate
Weight (lb/MFT)
N/A 4356 N/A 4761 N/A 5291 N/A 5895 N/A 6430
Minimum
Bending
Radius
(in)
N/A 23 N/A 24 N/A 24 N/A 25 N/A 26
Ampacity
90ºC
in Duct
N/A 195 N/A 220 N/A 250 N/A 285 N/A 310
Ampacity
90ºC
in Air
N/A 215 N/A 245 N/A 285 N/A 325 N/A 360