Applications
Stranded 1350 aluminum conductors shown in this section of data are classified as follows:

Class AA For bare conductors usually used in overhead lines.

Class A For conductors to be covered with weather-resistant materials and for bare conductors where greater flexibility is required.

Compact strand conductor for use in bare overhead applications or for use with weather-resistant coverings or insulations is also available.
Classes refer to stranding and are an indication of relativemore
Unit of Measure
Items
Bare Aluminum

Bare Aluminum AAC

Bare Aluminum

Bare Aluminum AAC

Bare Aluminum

Bare Aluminum AAC

Bare Aluminum

Bare Aluminum AAC

Bare Aluminum

Bare Aluminum AAC
Size
(AWG or kcmil)
N/A 6 N/A 4 N/A 2 N/A 1 N/A 1/0
No. of Wires N/A 7
CLASS N/A A N/A A N/A A AA N/A A AA N/A A AA
Diameter
Individual
Wire
N/A 0.0612 Inches N/A 0.0772 Inches N/A 0.0974 Inches N/A 0.1093 Inches N/A 0.1228 Inches
Diameter
Complete
Cable
(O.D.)
N/A 0.184 Inches N/A 0.232 Inches N/A 0.292 Inches N/A 0.328 Inches N/A 0.368 Inches
Cross
Sectional
Area
N/A 0.0206 sq.inches N/A 0.0328 sq.inches N/A 0.0521 sq.inches N/A 0.0657 sq.inches N/A 0.0829 sq.inches
Weight
(lb/1000 ft)
N/A 24.6 Lbs N/A 39.2 Lbs N/A 62.3 Lbs N/A 99.1 Lbs N/A 78.5 Lbs
Rated
Breaking
Strength
N/A 563 Lbs N/A 881 Lbs N/A 1350 Lbs N/A 1640 Lbs N/A 1990 Lbs
Resistance
DC
20 ºC
Per MFT
(ohm)
N/A 0.658 Ω N/A 0.414 Ω N/A 0.260 Ω N/A 0.207 Ω N/A 0.164 Ω
Resistance
AC
75 ºC
per MFT
(ohm)
N/A 0.805 Ω N/A 0.506 Ω N/A 0.318 Ω N/A 0.252 Ω N/A 0.202 Ω
Rating N/A 103 Amps N/A 138 Amps N/A 185 Amps N/A 214 Amps N/A 247 Amps