Applications
Directly buried or installed in ducts for 600 volt secondary distribution.

Construction
Concentric stranded or compressed 1350-H19 aluminum conductor, cross-linked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Black neutrals may be specified if desired.

Standards
Secondary URD duplex conductor 600V cable meets or exceeds the following ASTM specifications.
  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
  • B-231 Aluminum 1350
  • more
Unit of Measure
Items
Duplex Conductor Type URD Cable<br>Aluminum Conductor

Duplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor

Duplex Conductor Type URD Cable<br>Aluminum Conductor

Duplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor

Duplex Conductor Type URD Cable<br>Aluminum Conductor

Duplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor

Duplex Conductor Type URD Cable<br>Aluminum Conductor

Duplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor
Phase
Conductor
Size/AWG
N/A 8 N/A 6 N/A 4 N/A 2
Phase
Conductor
Stranding
N/A 7/w
Phase
Conductor
Insulation
Thickness
N/A 60 mls
Neutral Size AWG N/A 8 N/A 6 N/A 4 N/A 2
Neutral Stranding N/A 7/w
Neutral Insulation Thickness N/A 60 mls
Single
Phase
Conductor
N/A .262 Inches N/A .299 Inches N/A .345 Inches N/A .403 Inches
Outside
Diameter
N/A .524 Inches N/A .596 Inches N/A .690 Inches N/A .806 Inches
Weight
(lb/1000 ft)
N/A 76 Lbs N/A 91 Lbs N/A 129 Lbs N/A 189 Lbs
Ampacity
Direct Burial
N/A 70 Amps N/A 95 Amps N/A 125 Amps N/A 187 Amps
Ampacity
In Duct
N/A 70 Amps N/A 70 Amps N/A 90 Amps N/A 100 Amps