Applications
Used to supply 3 phase power, usually from a pole- mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75 ºC for polyethylene insulated conductors or 90 ºC for crosslinked polyethylene (XLP) insulated conductors.

Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded ACSR. One conductor is manufactured with an extruded ridge for phase identification.

Standards
  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
  • B-231 Aluminum conductors, Concentric-Lay-Stranded.
  • B-232 Aluminum Conductors, Concentric- Lay-Stranded, Coated Steel Reinforced (ACSR).
  • B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors.
  • B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
  • Quadruplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
Note :
Designated sizes are : ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTMB-399 for 6201.Conductor temperature of 90 ºC for XLR 75 ºC for Poly; ambient temperatures of 40 ºC emissivity 0.9; 2ft./sec/wind in sun. To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.
Unit of Measure
Items
Quadruplex Service Drop Cable<br>Aluminum Conductor

Quadruplex Service Drop Aluminum Conductors - ACSR Neutral-Messenger

Quadruplex Service Drop Cable<br>Aluminum Conductor

Quadruplex Service Drop Aluminum Conductors - ACSR Neutral-Messenger

Quadruplex Service Drop Cable<br>Aluminum Conductor

Quadruplex Service Drop Aluminum Conductors - ACSR Neutral-Messenger

Quadruplex Service Drop Cable<br>Aluminum Conductor

Quadruplex Service Drop Aluminum Conductors - ACSR Neutral-Messenger

Quadruplex Service Drop Cable<br>Aluminum Conductor

Quadruplex Service Drop Aluminum Conductors - ACSR Neutral-Messenger
Phase
Conductor
Size/AWG
N/A 6 N/A 6 N/A 4 N/A 4 N/A 2
Phase
Conductor
Stranding
N/A Solid N/A 7/w N/A Solid N/A 7/w N/A 7/w
Phase
Conductor
Insulation
Thickness
N/A 45 mls
Bare
Neutral
Messenger
Size/AWG
N/A 6 N/A 6 N/A 4 N/A 4 N/A 2
Bare
Neutral
Messenger
Stranding
N/A 6/1
Bare
Neutral
Messenger
Breaking
Strength
N/A 1190 Lbs N/A 1190 Lbs N/A 1860 Lbs N/A 1860 Lbs N/A 2850 Lbs
Weight
Per
(lb/1000 ft)
XLP
N/A 152 Lbs N/A 162 Lbs N/A 226 Lbs N/A 241 Lbs N/A 362 Lbs
Weight
(lb/1000 ft)
Poly
N/A 147.4 Lbs N/A 151.7 Lbs N/A 220 Lbs N/A 226.1 Lbs N/A 342.6 Lbs
Ampacity
XLP
N/A 75 Amps N/A 75 Amps N/A 100 Amps N/A 100 Amps N/A 135 Amps
Ampacity
Poly
N/A 60 Amps N/A 60 Amps N/A 80 Amps N/A 80 Amps N/A 105 Amps