Applications
Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts.

Construction
Concentric stranded or compressed 8000 (8176-H24) aluminum conductors, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Two phase and one neutral conductor twisted together (LH lay) to produce the triplex cable configuration, or parallel if so specified. Black neutrals may be specified if desired.

Standards
more
Unit of Measure
Items
Triplex Conductor Type URD Cable<br>Aluminum Conductor

Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor

Triplex Conductor Type URD Cable<br>Aluminum Conductor

Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor

Triplex Conductor Type URD Cable<br>Aluminum Conductor

Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor

Triplex Conductor Type URD Cable<br>Aluminum Conductor

Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor

Triplex Conductor Type URD Cable<br>Aluminum Conductor

Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor
Phase
Conductor
Size/AWG
N/A 6 N/A 4 N/A 2 N/A 2 N/A 1/0
Phase
Conductor
Stranding
N/A 7/w N/A 7/w N/A 7/w N/A 7/w N/A 19/w
Phase
Conductor
Insulation
Thickness
N/A 60 mls N/A 60 mls N/A 60 mls N/A 60 mls N/A 80 mls
Neutral Size AWG N/A 6 N/A 4 N/A 4 N/A 2 N/A 2
Neutral Stranding N/A 7/w
Neutral Insulation Thickness N/A 60 mls
Single
Phase
Conductor
N/A .299 Inches N/A .345 Inches N/A .403 Inches N/A .403 Inches N/A .522 Inches
Outside
Diameter
N/A .646 Inches N/A .754 Inches N/A .842 Inches N/A .874 Inches N/A 1.064 Inches
Weight
(lb/1000 ft)
N/A 143 Lbs N/A 203 Lbs N/A 264 Lbs N/A 294 Lbs N/A 408 Lbs
Ampacity
Direct Burial
N/A 95 Amps N/A 125 Amps N/A 165 Amps N/A 165 Amps N/A 215 Amps
Ampacity
In Duct
N/A 70 Amps N/A 90 Amps N/A 120 Amps N/A 120 Amps N/A 160 Amps