Applications
Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts.

Construction
Conductors are stranded or compressed 1350-H19 aluminum conductors, cross-linked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Two phase and one neutral conductor twisted together (LH lay) to produce the triplex cable configuration, or parallel if so specified. Black neutrals may be specified if desired.

Standards
Secondary URD triplex conductor 600V cable meets or exceeds the following ASTM specifications.
  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
  • B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
  • B-786 19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation.
  • B-901 Compressed round stranded Aluminum Conductors using single input wire construction.
  • Secondary UD triplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
  • "USE-2" per UL 854 available upon request.
Options
  • Cable in Duct (CIC)
  • Abrasion Resistant


Ampacity
90ºC conductor temperature, 20ºC ambient, RHO 50, 100% load factor for three conductors triplex with neutral carrying only unbalanced load. Technical data for cable with solid black neutral is identical to yellow extruded stripe data. All yellow extruded stripe cable is XLP insulation. To determine correct ampacity by conductor size, please consult the National Electric Code, the latest edition.
Unit of Measure
Items
Triplex Conductor Type URD Cable<br>Aluminum Conductor

Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor

Triplex Conductor Type URD Cable<br>Aluminum Conductor

Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor

Triplex Conductor Type URD Cable<br>Aluminum Conductor

Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor

Triplex Conductor Type URD Cable<br>Aluminum Conductor

Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor

Triplex Conductor Type URD Cable<br>Aluminum Conductor

Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor
Phase
Conductor
Size/AWG
N/A 6 N/A 4 N/A 2 N/A 2 N/A 1/0
Phase
Conductor
Stranding
N/A 7/w N/A 7/w N/A 7/w N/A 7/w N/A 19/w
Phase
Conductor
Insulation
Thickness
N/A 60 mls N/A 60 mls N/A 60 mls N/A 60 mls N/A 80 mls
Neutral Size AWG N/A 6 N/A 4 N/A 4 N/A 2 N/A 2
Neutral Stranding N/A 7/w
Neutral Insulation Thickness N/A 60 mls
Single
Phase
Conductor
N/A .299 Inches N/A .345 Inches N/A .403 Inches N/A .403 Inches N/A .522 Inches
Outside
Diameter
N/A .646 Inches N/A .754 Inches N/A .842 Inches N/A .874 Inches N/A 1.064 Inches
Weight
(lb/1000 ft)
N/A 143 Lbs N/A 203 Lbs N/A 264 Lbs N/A 294 Lbs N/A 408 Lbs
Ampacity
Direct Burial
N/A 95 Amps N/A 125 Amps N/A 165 Amps N/A 165 Amps N/A 215 Amps
Ampacity
In Duct
N/A 70 Amps N/A 90 Amps N/A 120 Amps N/A 120 Amps N/A 160 Amps