Applications
This cable is designed for high voltage connections between power distribution systems in mines, mine tunnels, shafts, and mine load centers where continuous monitoring of the ground system is required. This cable is suitable for installation in Ducts, troughs, tray or direct burial for non-flexing service.

Construction
  • Conductor is stranded annealed copper enveloped in a strand shield.
  • Insulation is Ethylene Propylene Rubber (EPR) or Cross Linked Polyethylene (XLPE).
  • Assembly is semi-conducting tape and a metallic tape shield with grounding conductors consisting of two bare grounds and one 8-gauge insulated ground check that are cabled together in the interstices of the power conductors and fillers are added to make round.
  • A single faced rubber filled tape is applied overlapped.
  • Jacket is Chlorinated Polyethylene (CPE).
Standards
Conforms to ICEA S-66-524 (NEMA WC8).

Notes
  • Shipping tolerance +/- 10%
Unit of Measure
Items
Image

Type MP-GC 3-Conductor - EPR/CPE or XLP/CPE 5kV) 100% Insulation Level (Grounded) 90°C

Image

Type MP-GC 3-Conductor - EPR/CPE or XLP/CPE 5kV) 100% Insulation Level (Grounded) 90°C

Image

Type MP-GC 3-Conductor - EPR/CPE or XLP/CPE 5kV) 100% Insulation Level (Grounded) 90°C

Image

Type MP-GC 3-Conductor - EPR/CPE or XLP/CPE 5kV) 100% Insulation Level (Grounded) 90°C

Image

Type MP-GC 3-Conductor - EPR/CPE or XLP/CPE 5kV) 100% Insulation Level (Grounded) 90°C
Power
Conductors
Size AWG
N/A 4 N/A 2 N/A 1/0 N/A 2/0 N/A 4/0
Power
Conductors
# of Strands
N/A 7 N/A 7 N/A 19 N/A 19 N/A 19
Power
Conductors
Insulation
Thickness
N/A .090 Inches
Ground Wire
Size AWG
N/A 7 N/A 5 N/A 3 N/A 2 N/A 1/0
Ground Wire
# of Strands
N/A 7 N/A 7 N/A 7 N/A 7 N/A 19
Overall
Diameter
N/A .110 Inches N/A .110 Inches N/A .110 Inches N/A .140 Inches N/A .140 Inches
Jacket
Thickness
(Inches)
N/A 1.32 N/A 1.45 N/A 1.63 N/A 1.75 N/A 2.00
Net Weight
Per MFT
N/A 1240 Lbs N/A 1670 Lbs N/A 2300 Lbs N/A 2730 Lbs N/A 3490 Lbs