Applications
This cable is designed for heavy-duty high voltage portable power trailing cable between the load center and equipment such as power shovels, draglines, and other excavators and is suitable for use in open pit mines, quarries and on gantry cranes where the delivery of a heavy power load and maximum safety is required.

Construction
  • Conductor is extra flexible, stranded, tinned annealed copper.
  • Insulation is Ethylene Propylene Rubber (EPR).
  • Covered grounding and 8-gauge ground check conductors.
  • Jacket is Black Chlorinated Polyethylene (CPE).
Standards
Conforms to ICEA S-68-516 (NEMA WC8).

Notes
  • Neoprene jacket optional.
  • Shipping tolerance +/- 10%
Unit of Measure
Items
Image

Type SHD-GC 3-Conductor EPR/CPE 5kV 100% Insulation Level - 90°C

Image

Type SHD-GC 3-Conductor EPR/CPE 5kV 100% Insulation Level - 90°C

Image

Type SHD-GC 3-Conductor EPR/CPE 5kV 100% Insulation Level - 90°C

Image

Type SHD-GC 3-Conductor EPR/CPE 5kV 100% Insulation Level - 90°C

Image

Type SHD-GC 3-Conductor EPR/CPE 5kV 100% Insulation Level - 90°C
Power
Conductors
Size AWG
N/A 6 N/A 4 N/A 2 N/A 1/0 N/A 2/0
Power
Conductors
# of Strands
N/A 133 N/A 133 N/A 259 N/A 266 N/A 342
Power
Conductors
Insulation
Thickness
N/A .070 Inches N/A .070 Inches N/A .070 Inches N/A .080 Inches N/A .080 Inches
Ground Wire
Size AWG
N/A 10 N/A 8 N/A 6 N/A 4 N/A 2
Ground Wire
# of Strands
N/A 19 N/A 133 N/A 133 N/A 133 N/A 133
Jacket
Thickness
(Inches)
N/A .155 N/A .155 N/A .170 N/A .190 N/A .250
Net Weight
Per MFT
N/A 960 Lbs N/A 1410 Lbs N/A 1940 Lbs N/A 2950 Lbs N/A 3470 Lbs