Applications
Stranded 1350 aluminum conductors shown in this section of data are classified as follows:

Class AA For bare conductors usually used in overhead lines.

Class A For conductors to be covered with weather-resistant materials and for bare conductors where greater flexibility is required.

Compact strand conductor for use in bare overhead applications or for use with weather-resistant coverings or insulations is also available.
Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible.

Construction
Aluminum alloy 1350-H19 wires, concentrically stranded.

Specifications
AAC bare conductors meet or exceed the following ASTM specifications :

B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-400 Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors

Notes
  • Resistance is calculated using ASTM standard increments of stranding and metal conductivity of 52.5% IACS, AC resistance at 60Hz
  • Current ratings are based on 75 ºC conductor temperature, 25 ºC ambient, 2ft/s wind, 96/watts/sq.ft sun, .05 coefficients of emissivity and absorption.
Unit of Measure

Specifications

Code Name

Heuchera

Size
(AWG or kcmil)

650

No. of Wires

37

CLASS

AA

Diameter
Individual
Wire

0.1326 Inches

Diameter
Complete
Cable
(O.D.)

0.928 Inches

Cross
Sectional
Area

0.5105 sq.inches

Weight
(lb/1000 ft)

610.2 Lbs

Rated
Breaking
Strength

11600 Lbs

Resistance
DC
20 ºC
Per MFT
(ohm)

0.0266 Ω

Resistance
AC
75 ºC
per MFT
(ohm)

0.0328 Ω

Rating

775 Amps

Standard Package Length (Feet)

6065 ft.12130 ft.

Standard Package Weight (Lbs.)

3700 Lbs7400 Lbs

Reel Size

RMT84.45 NR 66.28 RM 66.32 NR STL 71.46 NR STL 87.51