Applications
AA-8000 SER is Type SE, Style R cable, used as an above ground service entrance cable, a panel feeder and in branch circuits. The cable is rated at 600 volts and 90ºC for use in wet and dry locations in accordance with NEC Article 338.
Construction
Conductor: Compact stranded AA-8000 series aluminum conductor material per ASTM B800, ASTM B801, ASTM B836, ASTM B901 (Single Input Wire), as applicable.
Insulation: Color coded cross-linked polyethylene (XLPE).
Assembly: Insulated conductors are cabled with the bare ground wire. A flame retardant fiberglass reinforced binder tape assembles the core in a circular configuration.
Jacket: Sunlight resistant, RoHS compliant, flame retardant, gray polyvinyl chloride (PVC) material.
Conductor Identification:
3 Conductor Color coded: Black, White and Red
4 Conductor Color coded: Black, White, Red and Blue
Surface Print Legend: [manufacturer] 8000 TYPE SE - STYLE: R 600V XHHW AA-8000-AL [SIZE] AWG (UL) E-xxxxxx SUN RES ROHS (MFG. DATE) (SEQUENTIAL MARKING IN FEET)
Standards
- UL 44
- UL 854: Service Entrance Cables
- Federal specification JC-30B NEC
- RoHS compliant
Packaging
- 250 ft reels
- 500 ft reels
- 1000 ft reels
- Master reels
- Coils
Ampacity
To determine correct ampacity by conductor size, please consult the National Electric Code, Latest edition.
Items |
![]() A8-02SER8 Type SE Aluminum Cable (SER) |
![]() A6-02SER6 Type SE Aluminum Cable (SER) |
![]() A4-02SER6 Type SE Aluminum Cable (SER) |
![]() A4-02SER4 Type SE Aluminum Cable (SER) |
![]() A2-02SER4 Type SE Aluminum Cable (SER) |
|||||
Number of Conductors |
N/A 2 | |||||||||
Bare Ground Conductor Size |
N/A 8 | N/A 6 | N/A 6 | N/A 4 | N/A 4 | |||||
Nominal O.D. |
N/A 0.49 | N/A 0.57 | N/A 0.63 | N/A 0.67 | N/A 0.75 | |||||
Approximate Weight lbs/MFT |
N/A 97 | N/A 138 | N/A 177 | N/A 193 | N/A 254 | |||||
Amps 90ºC |
N/A 45 | N/A 60 | N/A 75 | N/A 75 | N/A 100 | |||||
Ampacity In Dwelling 90ºC (amps) |